Connection diagrams, Electrical installation, 30 electrical installation – Omega Engineering CN9400 User Manual

Page 34: Model cn9412 typical connection diagram

background image

Electrical Installation

30

ELECTRICAL INSTALLATION

(continued)

EN61010 - /CSA 22.2 No 1010.1 92

Compliance shall not be impaired when fitted to the final

installation.

Designed to offer a minimum of Basic Insulation only.

The body responsible for the installation is to ensure that

supplementary insulation suitable for Installation Category II or III is

achieved when fully installed.

To avoid possible hazards, accessible conductive parts of the final

installation should be protectively earthed in accordance with

EN6010 for Class 1 Equipment.

Output wiring should be within a Protectively Earthed cabinet.

Sensor sheaths should be bonded to protective earth or not be

accessible.

Live parts should not be accessible without the use of a tool.

When fitted to the final installation, an IEC/CSA APPROVED

disconnecting device should be used to disconnect both LINE and

NEUTRAL conductors simultaneously.

A clear instruction shall be provided not to position the equipment

so that it is difficult to operate the disconnecting device.

MODEL CN9412
TYPICAL CONNECTION DIAGRAM

The SSR driver output is allocated to SP1 and wired to switch the

load (heater) using an SSR

F1 Fuse:

time lag type to IEC127. CSA/UL rating 250Vac

F2 Fuse:

High Rupture Capacity (HRC) Suitable for

maximum rated load current

S1 Switch:

IEC/CSA/UL Approved disconnecting Device

Comms option

(when fitted)

1

2

3

4

5

6

7

8

L

N

5Vdc 15mA

+

+

12

13

14

15

16

Sensor

Output

SP1

SP2

Output

SSR

+

S1

Sensor

Supply

Line

Open in

alarm

state

9

10

11

Load

F2

F1

Neutral