Page 16

background image

The second setpoint SP2 can be used to trigger an alarm

or as a proportional control output.

TO CONFIGURE SP2 AS AN ALARM

Enter program mode.

Select level 2

then followed by the required option below:

dV.hi

sets off alarm signal when temperature rises above a

pre-set temperature above the setpoint.

dV.Lo

sets off alarm signal when temperature falls below a pre-set

temperature below the setpoint.

bAnd

sets off alarm signal when temperature rises above or falls

below a pre-set temperature above or below the setpoint.

FS.hi

sets off alarm signal when the temperature rises above

setpoint to a pre-set temperature above scale minimum.

FS.Lo

sets off alarm signal when the temperature falls below

setpoint to a pre-set temperature above scale minimum.

Select level 1

and set the required setpoint value (y°).

If the factory set hysteresis 2.0°C/3.6°F is unsuitable:

Index to

and adjust the setting.

Check

is set to

on.oF

(for alarm).

Exit program mode. SP2 is now operational as an alarm.

CooL

see heat-cool configuration, page 23.

Second Setpoint

SECOND SETPOINT (SP2)

Y

°

Deviation

high alarm

Deviation

low alarm

Deviation

band alarm

Alarm

state

SP

setpoint

Y

°

Y

°

Y

°

SP

setpoint

SP

setpoint

Y

°

= SP2

set value

Y

°

Full scale

high alarm

Full scale

low alarm

SP

setpoint

SP

setpoint

Y

°

12

SP2.A

NONE

SET.2

0

BND.2

CYC.2