Programmer

RAMP-SOAK

This feature enables the controller to ramp up or down from current

temperature to a target setpoint at a pre-determined rate. It then

controls at the target setpoint for an adjustable soak period before

switching off the heat output.

Set Ramp rate (0 to 9995 deg/hour)

Press ▲ and ▼ buttons for 3 seconds to enter

program entry point

Press ▲ to scroll to

Press and hold ✱, then press ▲ or ▼ to scroll to

required ramp value in the lower display

Set Soak (if required) 0 to 1440 minutes

Press ▲ to scroll to

Press and hold ✱, then press ▲ or ▼ to scroll to

required soak period in the lower display.

Set Ramp On

(Off) : On : hold

Press ▲ to scroll to

Press and hold ✱, then press ▲ to select On

Exit program to enter settings into memory and commence ramp to

target setpoint.

Notes

In Ramp on configuration, if power is removed from the controller,

the Ramp will re-start when power is restored.

The Ramp hold option suspends the ramp at its last value.

If no Soak period has been set, control at target setpoint continues

indefinitely.

SP2 deviation alarms follow the ramp setpoint and can be used to

alarm “out of limits” ramp rate.

WARNING

The Soak timer is triggered when the ramp setpoint reaches the

target setpoint. If the ramp rate is set too fast for the process, the

Soak timer will be triggered before the process temperature reaches

the target setpoint.