Error Messages

ERROR MESSAGES

Temp

Setpoint

Cycle

75% SP

Start

TUNE

TUNE

Tuning

DAC

PID

New PID
values
entered

Time

(100% output)

oS 1

oS 2

Ct A

Ct b

Ct 3

Ct 4

uS

Ct 1

Ct 2

SENSOR FAULT

Upper display alternates:

inPt

and

FAiL

Indicates: thermocouple burnout RTD/Pt100 open or

short circuit or negative over-range.

Action:

Check sensor/wiring

NON-VOLATILE MEMORY ERROR

Upper display alternates:

dAtA

and

FAiL

Action:

De-power briefly. Replace unit if problem

persists

MANUAL POWER ERROR

Upper display alternates:

hAnd

and

FAiL

SP1 set to ON/OFF in

CYC.t

Action: Select proportional mode

IMMEDIATE FAIL ON AUTOTUNE START

Upper display alternates:

PV tunE

and

FAiL

Lower display 0

1. No setpoint entered.

Action: Enter setpoint

2. SP1 set to ON/OFF in

Action: Select proportional mode

Note:

To reset and clear error press ▲▼ together
briefly to cancel message.

FAIL LATER DURING AUTOTUNE CYCLE

The thermal characteristics of the load exceed the

Autotune algorithm limits. The failure point indicated

by any display 0.0 in

e.g. Ctb = 0.0 see adjacent diagram.

Action:

1.

Change the conditions. eg. raise setpoint

2.

Try

3. Check SP1.P percentage power

(see IMPROVING CONTROL ACCURACY)

4. If the error message persists, call CAL

for advice.

READING AUTOTUNE TUNING CYCLE
RESULTS IN

tECh

1. Index to

release ▲ or ▼, lower display will alternate

Ct.A

and value

2. Keep ✱ pressed and press ▲ once, the lower

display will alternate

Ct.b

and value (eg. 19.6)

3. Repeat step 3 above to view:

Ct 1, Ct 2, Ct 3, Ct 4, oS 1, uS

and

oS 2

.

Autotune tuning data and limits

14

INPT

DATA

HAND

FAIL

0

CYC.T

ON.OF

TECH

TUNE

AT.SP

TECH

CT.A