Function list – Omega Engineering CN9400 User Manual
Page 24
Function List
F
unction Options
[Factory settings] shown in brackets
Select SP1/2 LED indicator modes
SP1
SP2
[1n.2n]
Normal
Normal
1i.2n
Invert
Normal
1n.2i
Normal
Invert
1i.2i
Invert
Invert
[0.0] to ±25% sensor maximum
Sensor span adjust
For recalibrating to a remote standard e.g. External
Meter, data logger. See ADVANCED SETTINGS page
[0.0] to ±25% sensor f/s
Zero sensor error, see SPAn
[oFF] on
Select control accuracy monitor
[
Var] hi Lo
Read control accuracy monitor
20
LEVEL 3 (continued)
F
unction Options
[Factory settings] shown in brackets
[
Ct A] CT b Ct 1 Ct 2 Ct 3
Ct 4 oS 1 uS oS 2
Read Autotune tuning cycle data (see figure, page 14)
Software version number
[nonE] ALL
Resets all functions to factory settings
Caution:
Note current configuration before using this
function, otherwise initial configuration and
OEM settings must be re-entered.
REU.L
TECH
VER
RSET
SPAN
ZERO
CHEK
READ