background image

Function List

Sensor burn-out/break protection

Caution: Settings affect fail safe state.

SP1

SP2

[uP.SC]

Upscale

Upscale

dn.SC

Downscale

Downscale

1u.2d

Upscale

Downscale

1d.2u

Downscale

Upscale

Select output modes: Direct/Reverse

Caution: Settings affect fail safe state.

SP1

SP2

[1r.2d]

Reverse

Direct

1d.2d

Direct

Direct

1r.2r

Reverse

Reverse

1d.2r

Direct

Reverse

Select Reverse on SP1 for heating and Direct for

cooling applications.

19

LEVEL 3

OUTPUT CONFIGURATION

Note: ‘Read only’ after initial configuration.

rSET ALL

full reset to

factory settings required to change subsequently.

F

unction Options

[Factory settings] shown in brackets

[nonE] rLY

SSd rLY1 rLY2 SSd1

Select SP1 output device

[nonE] SSd rLY

rLY2 rLY1 SSd2

Read SP2 output device

(read only)

Dual Relay and Dual SSd output options Models CN9411

and CN9422 are factory set. See page 22

Note: (when in initial configuration only)

Hold ✱ and ▲ or ▼ for 10 seconds to move to or from

output devices in shaded portion.

SP1.D

BURN

REU.D

SP1.D

SP2.D