background image

Function List

LEVEL 4

Access to level 4 is gained through in level 3.

Press and hold ▲ and ▼

for 10 seconds.

Enter level 4 at

Lock

, release ▲ and ▼ together.

Display reads

Program security using Lock

Select from three

Lock

options:

Press and hold ✱, press ▲ to index.

LEV.3

locks level 3 and 4 only- Technical Functions.

LEV.2

locks levels 2, 3 and 4 only - Configuration and

Technical Functions.

ALL

locks all functions

Note: Locked functions and options may be read.

F

unction Options

[Factory settings] shown in brackets

Press ▼ to access following functions

[Auto] StAY

Program mode auto-exit switch

Auto-exit returns display to normal if 60 seconds of

key inactivity, select

StAY

to disable

[oFF] on

Disable SP2 alarm annunciator -AL-

Select on to disable -AL-

dir 1 to 32 [6]

Display sensitivity

dir

= direct display of input

1

= maximum,

32

= minimum sensitivity

0.1 to 1.0 [0.5]

Derivative sensitivity

21

IMPORTANT NOTE FOR OEM’s: For safety and to protect settings from tampering

USE THE SOFTWARE SECURITY LOCK.... THEN REMOVE THIS SECTION.

VER

PROG

NO.AL

DIS.S

DER.S

LOCK

NONE

LOCK

ALL