Factory set output options, Output options, 22 dual relay or dual ssd output models – Omega Engineering CN9400 User Manual

Page 26: 3to select sp1

background image

FACTORY SET OUTPUT OPTIONS

22

DUAL RELAY OR DUAL SSd OUTPUT MODELS

The table below details the factory set output options. rLY2 is a 1A

electromechanical relay, and SSd1/SSd2 is an identical second SSR

drive output.

QUICK START (page 1a) or SET-UP (page 5) follow steps 1
and 2 ignore step 3 and proceed straight to step 4.

Factory Option CN9411 offers the ability to change the allocation of

SP1 to terminals 5 and 6.

To make this selection during the initial configuration in either

QUICK START (page 1b) or SET-UP (page 5), start from step 3.

3

TO SELECT SP1

(Main setpoint output device)

From the display

press and hold ✱ button then press the ▲ once

to display

rLY2

in the lower display.

Product

Code

Terminals

3

4

5

6

CN9411

CN9422

rLY1 (2A)

rLY2 (1A)

SSd1

SSd2

(+)

(-)

(+)

(-)

Factory Options CN9411 and CN9422 pre-allocate SP1 to
terminals 3 and 4.

Note:

Output device rLY/rLY1 is rated 2A
Output device rLY2 is rated 1A

SP1D

RLY1