Installation, Clearances – Regency P48-2 User Manual

Page 8

background image

Regency

®

P48-2 Zero Clearance Direct Vent Gas Fireplace

8

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fi replace and vent system be installed only in accordance with these instructions.

Clearance to Combustibles from:

Back 0"

(0mm)

Side 0"

(0mm)

Floor 0"

(0mm)

Minimum Clearance from Top of Front Facing:

Mantel min.

8"

(203mm)

Ceiling

39"

(990mm) from top of front facing

above

louvers.

Side Wall:

6"

(152mm)

Horizontal Vent Clearances:

Top

2-1/2" (64mm)

Side

1-1/2" (38mm)

Bottom

1-1/2" (38mm)

Vertical Vent Clearances:

1-1/4" (32mm)

Alcove Clearances:

Max. Depth 36"

(914mm)

Min. Width 60"

(1524mm)

Min. Height 80"

(2032mm)

INSTALLATION

The HeatWave Duct Kit
and the Heat Release Kit
have different clearance
and framin requirements,
check the HeatWave and
Heat Release manual for
details.

Heat Release Kit

Caution Requirements

The top, back and sides of the fi replace are defi ned by

standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this

fi replace and vent system be installed only in

accordance with these instructions.