Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

19

INSTALLATION

HORIZONTAL

INSTALLATIONS

Install the flue system according to the

manufacturer's instructions included

with the components.

1) Set the unit in its desired location. Check to

determine if wall studs or roof rafters are in

the way when the flueing system is at-

tached. If this is the case, you may want to

adjust the location of the unit. Rough in the

gas.

2) Direct Flue pipe and fittings are designed

with special twist-lock connections to con-

nect the flueing system to the appliance flue

outlet. A twist-lock appliance adaptor is an

available option that must be used in con-

junction with the Simpson Dura-Vent Direct

Vent GS system.

3) Put a bead of silicone inside the outer section

of the adapter and a bead of Mill Pac on the

inner collar. Slip the adapter over the exist-

ing inner and outer flue collar and fasten to

the outer collar only with the 3 supplied

screws (drilling pilot holes will make this

easier). Level the fireplace and fasten it to

the framing using nails or screws through

the nailing strips.

4) Assemble the desired combination of pipe

and elbows to the appliance adaptor and

twist-lock for a solid connection.

Note:

a) Twist-lock procedure: Four indentations,

located on the female ends of pipes and

fittings, are designed to slide straight

onto the male ends of adjacent pipes and

fittings, by orienting the four pipe inden-

tations so they match and slide in to the

four entry slots on the male ends, Dia-

Diagram 1

b) Horizontal runs of flue must be sup-

ported every three feet. Wall straps are

available for this purpose.

5) Mark the wall for a 10" x 10" square hole.

The center of the square hole should line up

with the centerline of the horizontal pipe.

Cut and frame the 10 inch square hole in the

exterior wall where the flue will be termi-

nated. If the wall being penetrated is con-

structed of non-combustible material, i.e.

masonry block or concrete, a 7"(178mm)

dia. (7-1/2"(191mm) dia. for flex) hole is

acceptable.

Note: With Dura-Vent, the minimum height

is achieved by installing a 45

o

elbow di-

rectly to the flue adaptor.

Diagram 2

Note:

a) The horizontal run of flue must be level,

or have a 1/4 inch rise for every 1 foot

of run towards the termination. Never

allow the flue to run downward. This

could cause high temperatures and

may present the possibility of a fire.

b) The location of the horizontal flue termi-

nation on an exterior wall must meet all

local and national building codes, and

must not be blocked or obstructed. For

External Flue Terminal Locations, see

diagram on page 12.

6) The arrow on the flue cap should be

pointing up. Insure that the 1-1/2" clear-

ances to combustible materials are main-

tained (Diagram 3 on page 16). Install the

termination cap.

The four wood screws provided should be

replaced with appropriate fasteners for

stucco, brick, concrete, or other types of

sidings.

Note: If installing termination on a siding

covered wall, a vinyl siding stand-

off or furring strips must be used

Note: Apply sealant "Mill-Pac" to inner

pipe and high temperature sili-

cone sealant to outer pipe on eve-

ry twist-lock joint.

Diagram 12

Vertical Flueing with Three (3) 90

o

Elbows

Option

V + V1

H + H1

A)

2' (610mm) Minimum

3' (914mm) Maximum

B)

3' (914mm) Minimum

6' (1.86m) Maximum

C)

4' (1.22m) Minimum

9' (2.7m) Maximum

D)

5' (1.5m) Minimum

12' (3.6m) Maximum

gram 1. Push the pipe sections com-

pletely together, then twist-lock one

section clockwise approximately one-

quarter turn, until the two sections are

fully locked. The female locking lugs will

not be visible from the outside, on the

Black Pipe or fittings. They may be

located by examining the inside of the

female ends.

With the above options, maximum total pipe length if 37 feet with

minimum of 5 feet total vertical and maximum 12 feet total horizontal.

Please note minimum 1 foot between 90

o

elbows is required.