Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

11

FLUEING

INTRODUCTION

The P121/P121LC/P121RC/P131 uses the

"balanced flue" technology Co Axial system.

The inner liner flue products of combustion to

the outside while the outer liner draws outside

combustion air into the combustion chamber

thereby eliminating the need to use heated room

air for combustion and losing warm room air up

the chimney.

Note: These flue pipes must not be con-

nected to any other appliance.

The gas appliance and flue system must be

flueed directly to the outside of the building, and

never be attached to a chimney serving a

separate solid fuel or gas burning appliance.

Each direct flue gas appliance must use it's

own separate flue system. Common flue sys-

tems are prohibited.

INSTALLATION

UNIT ASSEMBLY

PRIOR TO

INSTALLATION

The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped

into position.

Top Standoff Assembly

The top standoffs are shipped in a flat position and must be folded into shape and attached.

1) Remove the standoffs from the fireplace

top.

2) Take each standoff and bend into the

correct shape. Bend up at the bend lines

until the screw holes in the standoff and the

pre-punched screw holes on the fireplace

top line up.

3) Attach the standoff securely to the top with

4 screws per standoff (on opposite cor-

ners).

FACING & FINISHING REQUIREMENTS

This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non-

combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)