Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

15

INSTALLATION

FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS

SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (LPG & NG)

The diagram below shows examples of horizontal termination arrangements using one, two, or three 90

o

elbows (two 45

o

elbows equal one 90

o

elbow).

Note:

1) A maximum of three 90

o

elbows are permitted.

2) Minimum distance between elbows is 1 ft. (305mm).

•

Maintain clearances to combustibles as listed on page 9.

•

Horizontal flue must be supported every 3 feet.

•

Firestops are required at each floor level and whenever passing through a wall.

•

Must use optional flue adapter (Part# 510-994) when using Simpson Dura-Vent pipe.

•

A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.

Simpson Dura-Vent

4" inner diameter

6-5/8" outer diameter

Straight Out Horizontal Flueing

Horizontal Flueing with One (1) 90

o

Elbow

Option

V

H

A)

1' (305mm) Minimum

3' (914mm) Maximum

B)

2' (610mm) Minimum

6' (1.86m) Maximum

C)

3' (914mm) Minimum

9' (2.7m) Maximum

D)

4' (1.22m) Minimum

12' (3.6m) Maximum

E)

5' (1.5m) Minimum

15' (4.5m) Maximum

F)

6' (1.86m) Minimum

17' (5.1m) Maximum

Diagram 1

Diagram 2

With the above options, maximum total pipe length if 37 feet with

minimum of 6 feet total vertical and maximum 17 feet total horizontal.

Please note minimum 1 foot between 90

o

elbows is required.

Please note the minimum centerline

for basic install shown above.