beautypg.com

Installation, Exterior flue termination locations – Regency SEE THRU P121-NG User Manual

Page 12

background image

Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

12

INSTALLATION

EXTERIOR FLUE TERMINATION LOCATIONS

Minimum clearances required for balanced flue terminals or

the flue terminals of outdoor appliances

according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)

Minimum

Clearance (mm)

a Below eaves, balconies or other projections:

- Appliances up to 50 MJ/h input

300

- Appliances over 50 MJ/h input

500

b From the ground or above a balcony

300

c From a return wall or external corner

500

d From a gas meter (M)

1000

e From an electricity meter or fuse box (P)

500

f

From a drain or soil pipe

150

g Horizontal from any building structure (unless appliance is approved

for closer installation) or obstruction facing a terminal

500

h From any other flue terminal, cowl or combustion air intake

500

j

Horizontally from an openable window, door, or non-mechanical air inlet, or

any other opening into a building, with the exception of sub-floor ventilation

(see also Note (I)):

- Appliances up to 150 MJ/h input

500

- Appliances over 150 MJ/h input

1500

k Vertically below an openable window, door, or non-mechanical air inlet,

or any other opening into a building, with the exception of sub-floor ventilation

(see also Note (I)): see table below

Clearance 'k' in mm

Space Heaters

All Other Appliances

Up to 50 MJ/h

Up to 50 MJ/h input

Over 50 MJ/h input

Over 150 MJ/h input

input

to 150 MJ/h input

150

500

1000

1500

NOTES:

(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.

(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest

par to of the terminal.

(III) Prohibited area below electricity meter or fuse box extends to ground level.

(IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on

at least two sides and a free flow of air at the appliance is achieved.

This manual is related to the following products: