Installation, Ultraglow, Ultraglow ultraglow direct vent system (flex) – Regency G36D User Manual

Page 14: Propane & natural gas)

background image

UltraGlow

®

G36D Zero Clearance Direct Vent Gas Fireplace

®

®

14

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

UltraGlow

®

UltraGlow

UltraGlow DIRECT VENT SYSTEM (FLEX)

®

®

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90

using one 90

o

elbow (two 45

o

elbows equal one 90

o

elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid vent systems.

All Rigid Pipe Systems

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

UltraGlow

UltraGlow

®

UltraGlow

UltraGlow Flex Vent

®

®

4" inner diameter

6-7/8" inner diameter

• Maintain clearances to combustibles as listed in the "Clearances," "Mantel Leg Clearances," "Framing and Finishing," & "Combustible

Mantels" sections.

• Horizontal vent must be supported every 3 feet.

• Firestops are required at each fl oor level and whenever passing through a wall.

A vent guard should be used

whenever the termination is lower

than the specifi ed minimum or as

per local codes.

Note: UltraGlow

®

Direct Vent System

®

®

(Flex) is only approved for

horizontal terminations.

INSTALLATION