Installation, Ultraglow, Ultraglow ultraglow direct vent system (flex) – Regency G36D User Manual
Page 14: Propane & natural gas)
UltraGlow
®
G36D Zero Clearance Direct Vent Gas Fireplace
®
®
14
RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
UltraGlow
®
UltraGlow
UltraGlow DIRECT VENT SYSTEM (FLEX)
®
®
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
using one 90
o
elbow (two 45
o
elbows equal one 90
o
elbow).
Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid vent systems.
All Rigid Pipe Systems
All Rigid Pipe Systems
4" inner diameter
6-5/8" outer diameter
UltraGlow
UltraGlow
®
UltraGlow
UltraGlow Flex Vent
®
®
4" inner diameter
6-7/8" inner diameter
• Maintain clearances to combustibles as listed in the "Clearances," "Mantel Leg Clearances," "Framing and Finishing," & "Combustible
Mantels" sections.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
A vent guard should be used
whenever the termination is lower
than the specifi ed minimum or as
per local codes.
Note: UltraGlow
®
Direct Vent System
®
®
(Flex) is only approved for
horizontal terminations.
INSTALLATION