UltraGlow

®

G36D Zero Clearance Direct Vent Gas Fireplace

15

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

UltraGlow

®

UltraGlow

UltraGlow DIRECT VENT SYSTEM (FLEX)

®

®

(Propane & Natural Gas)

The diagram below shows examples of horizontal termination arrangements using two 90

o

elbows (two 45

o

elbows equal one 90

o

elbow).

Note:

1) A maximum of two 90

o

elbows are permitted.

2) A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90

o

elbows are used.

3) Minimum distance between elbows is 2 ft. (0.6m).

4) Determine the permitted range of horizontal termination arrangements by using chart in the "Rigid Pepi Venting

Arrangements - Vertical Termination" section and deducting 3 ft. (0.9m) from the maximum horizontal distance for the

second 90

o

elbow.

All Rigid Pipe Systems

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

UltraGlow

UltraGlow

®

UltraGlow

UltraGlow Flex Vent

®

®

4" inner diameter

6-7/8" inner diameter

• Maintain clearances to combustibles as listed in the "Clearances," "Locating Your Gas Stoves," "Combustible Mantels," "Framing

and Finishing," & "Hearth Requirement" sections.

• Horizontal vent must be supported every 3 feet.

A vent guard should be used whenever the

termination is lower than the specifi ed minimum

or as per local codes.

If length "B" is increased, length "A" must be

decreased by a corresponding amount.