Temperature – Perle Systems IOLAN SCS User Manual
Page 259

259
Channels
Temperature
Temperature input channels monitor RTD or thermocouple temperature sensors inputs for the most
common ranges. You can also configure severity alarms that can send an email, a syslog message,
and/or an SNMP trap when an alarm is triggered or cleared; See
for
more information about the alarms.
RTD ranges are:
Thermocouple ranges are:
In the following example, a Temperature I/O IOLAN is used to monitor industrial freezer
temperature sensors, with an alarm set to send a syslog message if the temperature rises above 31
o
C.
z
Pt100 a=385 -50 to 150C
z
Pt100 a=392 -50 to 150C
z
Pt1000 a=385 -40 to 160C
z
Pt100 a=385 0 to 100C
z
Pt100 a=392 0 to 100C
z
NiFe604 a=518 -80 to 100C
z
Pt100 a=385 0 to 200C
z
Pt100 a=392 0 to 200C
z
NiFe604 a=518 0 to 100C
z
Pt100 a=385 0 to 400C
z
Pt100 a=392 0 to 400C
z
Pt100 a=385 -200 to 200C
z
Pt100 a=392 -200 to 200C
Note:
IEC RTD 100 ohms.=0.00385
JIS RTD 100 ohms.=0.00392
z
B 500 to 1800C
z
K 0 to 1370C
z
T -100 to 400C
z
E 0 to 1000C
z
R 500 to 1750C
z
J 0 to 760C
z
S 500 to 1750C
IOLAN
pe
rl
e
Monitoring
Application
Network
Industrial
Freezers
Temperature I/O
T4