Liebert iCOM Microprocessor TM-10098 User Manual
Page 98

iCOM
Control Training and Service Manual
098 DIG SCROLL2
HIGH TEMP
Digital Scroll compressor
#1 shut off because of
high temperature (sensor
is inside the
compressor).
Alarm
no
yes
yes
(broken co
will remain
off)
103 SHORT CYCLE compressors are
requested from control to
start too often - control is
unstable.
Message
- no
-
104 SMOKE
DETECTED
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
105 WATER
UNDER
FLOOR
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
106 COND PUMP-
HIGH WATER
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
107 LOSS OF
FLOW
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
108 STBY GLYCOL
PUMP ON
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
109 STANDBY
UNIT ON
customer input is active.
Alarm
no
yes
yes (if not
disabled
externally)
110 HW/HG HRS
EXCEEDED
actual working hours of
hot water heat / hot gas
reheat are higher than
the threshold set.
Warning
no
no
-
111 EL HEAT1 HRS
EXCEEDED
actual working hours of
electrical heater stage 1
are higher than the
threshold set.
Warning
no no
-
112 EL HEAT2 HRS
EXCEEDED
actual working hours of
electrical heater stage 2
are higher than the
threshold set.
Warning
no
no
-
113 EL HEAT3 HRS
EXCEEDED
actual working hours of
electrical heater stage 3
are higher than the
threshold set.
Warning
no no
-
97