Liebert iCOM Microprocessor TM-10098 User Manual
Page 78

iCOM
Control Training and Service Manual
Service Menu: Set Alarm Parameters: Page 3 of 6
Menu Line
Parameter
S223
Password
S224
DELAY
EN-DIS
TYPE
S225
Main Fan Overload
10 Sec
En
Alarm
S226
Loss of Airflow
10 Sec
En
Alarm
S227
Clogged Filters
60 Sec
En
Warning
S228
High Room Temperature
10 Sec
En
Warning
S229
Low Room Temperature
10 Sec
En
Warning
S230
High Room Humidity
10 Sec
En
Warning
S231
Low Room Humidity
10 Sec
En
Warning
S232
High Temp Sensor A
10 Sec
En
Warning
S233
Low Temp Sensor A
10 Sec
En
Warning
S234
High Humid Sensor A
10 Sec
En
Warning
S235
Low Humid Sensor A
10 Sec
En
Warning
Service Menu: Set Alarm Parameters: Page 4 of 6
Menu Line
Parameter
S236
Password
S237
DELAY
EN-DIS
TYPE
S238
Comp 1 Overload
10 Sec
En
Alarm
S239
Comp 2 Overload
10 Sec
En
Alarm
S240
Comp 1 High Pressure
-
En
Alarm
S241
Comp 1 High Pressure
-
En
Alarm
S242
Comp 1 Low Pressure
-
En
Alarm
S243
Comp 2 Low Pressure
-
En
Alarm
S244
Comp 1 Pumpdown Fail
-
En
Alarm
S245
Comp 2 Pumpdown Fail
-
En
Alarm
S246
Dig Scroll1 High Temp
-
En
Alarm
S247
Dig Scroll2 High Temp
Alarm
77