Liebert iCOM Microprocessor TM-10098 User Manual
Page 71

iCOM
Controls Training and Service Manual
Service Menu: Fan Settings Maintenance / Wellness Parameters: Page 2 of 8
Menu Line
Parameter
Default
Range
S012 Password
-
-
S013
Number of Starts
-
0 – 32000
S014
Run Hours
-
0 – 32000
S015
Average Working Time
-
0 – 999 minutes
S016
Starts per Day Optimum
1
1 – 240
S017
Starts per Day Worst
24
1 – 240
S018
Number of Alarms
-
0 – 32000
S019
Actual Bonus
-
0 - 12
Service Menu: Compressor 1 Settings Maintenance / Wellness Parameters:
Page 3 of 8
Menu Line
Parameter
Default
Range
S023 Password
-
-
S024
Number of Starts
-
0 – 32000
S025
Run Hours
-
0 – 32000
S026
Average Working Time
-
0 – 999 minutes
S027
Starts per Day Optimum
12
1 – 240
S028
Starts per Day Worst
240
1 – 240
S029
Number of HP Alarms
-
0 – 32000
S030
Number of LP Alarms
-
0 – 32000
S031
Number of OL Alarms
-
0 – 32000
S032
Number of DS HT Alarms
-
0 - 32000
S033
Actual Bonus
-
0 - 12
70