Liebert iCOM Microprocessor TM-10098 User Manual
Page 74

iCOM
Control Training and Service Manual
Service Menu: Humidifier Settings Maintenance / Wellness Parameters:
Page 8 of 8
Menu Line
Parameter
Default
Range
S078 Password
-
-
S079
Number of Starts
-
0 – 32000
S080
Run Hours
-
0 – 32000
S081
Average Run Time
-
0 – 999 minutes
S082
Starts per Day Optimum
24
1 – 240
S083
Starts per Day Worst
240
1 – 240
S084
Number of Alarms
-
0 – 32000
S085
Actual Bonus
-
0 - 12
Service Menu: Diagnostics / Service Mode S300 series: Page 1 of 5
Menu Line
Parameter
Range
S301 Password
-
S302
Manual Mode
Yes or No
S303 Motor(s)
Off
or
On
S304
Compressor 1
Off or On
S305
Compressor 1 Capacity
Off or On
S306
Compressor 1 Cycle Ramp
0-100%
S307
Compressor 1 LLSV
Off or On
S308
Compressor 2
S309
Compressor 2 Capacity
Off or On
S310
Compressor 2 Cycle Ramp
0 – 100%
S311
Compressor 2 LLSV
73