Liebert iCOM Microprocessor TM-10098 User Manual
Page 88

iCOM
Control Training and Service Manual
Advanced Menu: Factory Settings Parameters: Page 6 of 6
Menu Code
Parameter
Default
Range
A145
Password
-
-
A146
Humidifier Model
No
No, external, IFS, IFL
A147
Humidity in Last
xx Hours
15hr
1 - 120 hours
A148
Prefill Time
IFS 30
IFL 60
1 - 120 seconds
A149
Fill Time
IFS 30
IFL 50
1 - 120 seconds
A150
Humidifier On
Time
IFS 8
IFL 10
1 - 60 minutes
A151
Dehum with
Compressor
2
1, 2, both
A152
Analog Output 1
Not used
* See note 3
A153
Analog Output 2
Not used
*See note 3
A154
Analog Output 3
Not used
* See note 3
A155
Analog Output 4
Not used
* See note 3
Note 1: LP threshold Phase 1 (A117):
If condenser ctrl (A132) = fan speed then setting is 50 psiA ; otherwise 75 psiA.
If the condenser control setting changes, the setting for A117 will be updated
automatically. If any of the sources (Refrigerant, Freecooling, Hotwater) changes,
the setting for A118 will be updated automatically.
Note 2: LP threshold Phase 1 (A118):
R22 (A102) + NO FC (A137) + NO Hotwater (S408) = 63 psiA
R22 (A102) + YES FC (A137) + NO Hotwater (S408) = 68 psiA
R22 (A102) + NO FC (A137) + YES Hotwater (S408) = 75 psiA
R22 (A102) + YES FC (A137) + YES Hotwater (S408) = 75 psiA
R407c (A102) + NO FC (A137) + NO Hotwater (S408) = 70 psiA
R407c (A102) + YES FC (A137) + NO Hotwater (S408) = 75 psiA
R407c (A102) + NO FC (A137) + YES Hotwater (S408) = 83 psiA
R407c (A102) + YES FC (A137) + YES Hotwater (S408) = 83 psiA
Note 3: The following components may be controlled with the Analog Outputs and
labeled as: Hot Water Reheat, 3P Valve, Fan Speed, Cooling, Cooling 1, Cooling
2, Heating and Not Used.
87