iCOM
Controls Training and Service Manual
Advanced Menu: Factory Settings Parameters: Page 4 of 6
Advanced Menu: Factory Settings Parameters A100 series: Page 5 of 6
Menu Code
Parameter
Default
Range
A123
Password
-
-
A124
LP1 Sensor
10%
0 - 100%
A125
LP1 Signal
150 psiA
-87.0 to +725 psiA
A126
Actual LP1 Signal
-
0 - 100%
A127
LP2 Sensor
10%
0 - 100%
A128
LP2 Signal
150 psiA
-87.0 to +725 psiA
A129
Actual LP2 Signal
-
0 - 100%
A130
Pumpdown Cutout
35 psiA
0.0 - 145 psiA
A131
Pumpdown Recycle
80 psiA
0.0 - 145 psiA
A132
Heat Rejection Control
Type
Fan Speed
Fan Speed /
Lee-Temp / Glycol
Menu Code
Parameter
Default
Range
A134
Password
-
-
A135
A136
CW flush Duration
0
No, 1 - 3 min
A137
Freecooling
No
No, Yes
A138
A139
Freecooling Flush Duration
0
No, 1 - 3 min
A140
Freecooling Flush Starts R5
Yes
No, Yes
A141
CO + FC simultaneously
Yes
No, Yes
A142
A143
Hot water flush duration
0
No, 1 - 3 min
86