User menu: set alarm parameters u200 series – Liebert iCOM Microprocessor TM-10098 User Manual
Page 64

iCOM
Control Training and Service Manual
User Menu: Set Alarm Parameters U200 series
Menu Line
Parameter
Default
Range
U201 Password
-
-
U202
Return Sensor Alarms
Enabled
Enabled or Disabled
U203
High Return Temperature
80ºF
33 - 210ºF
U204
Low Return Temperature
60ºF
33 - 210ºF
U205
High Return Humidity
60%
1 – 99%
U206
Low Return Humidity
40%
1 – 99%
U207
Sensor A Alarms
Disabled
Disabled or Enabled
U208
High Temperature Sensor A
90ºF
33 - 210ºF
U209
Low Temperature Sensor A
55ºF
33 - 210ºF
U210
High Humidity Sensor A
70%
1 - 99%
U211
Low Humidity Sensor A
30%
1 - 99%
User Menu: Sensor Data U300 series: Page 1 of 2
Menu Line
Parameter
Range
U301
Actual Temperature Setpoint
41 – 104ºF
U302
Actual Humidity Setpoint
20 – 80%
U303
Optional Sensor A Temperature
32 - 122ºF
U304
Optional Sensor A Humidity
20 – 80%
U305
Optional Sensor B Temperature
32 - 122ºF
U306
Optional Sensor B Humidity
20 – 80%
U307
Optional Sensor C Temperature
32 - 122ºF
U308
Optional Sensor C Humidity
20 – 80%
U309 Freecooling
Fluid
Temperature
4 - 113ºF
U310
DigiScroll 1 Temperature
84 - 313ºF
U311
DigiScroll 2 Temperature
84 - 313ºF
U312
Freecooling Status
Off, Start, On
63