Liebert iCOM Microprocessor TM-10098 User Manual
Page 81

iCOM
Controls Training and Service Manual
Service Menu: Sensor Calibration/ Setup Parameters: Page 3 of 3
Menu Line
Parameter
Default
Range
S623 Password
-
S624
Glycol sensor PTC or NTC
NTC
NTC or PTC
S625 Glycol
sensor
-
±17ºF
S626
Calibrated glycol sensor
-
4 – 113ºF
S627
Supply sensor PTC or NTC
NTC
NTC or PTC
S628
Supply sensor
-
±17ºF
S629
Calibrated supply sensor
-
32 - 122ºF
S630
Temperature sensor C
-
±17ºF
S631
Calibrated temperature sensor C
-
32 - 122ºF
S632
Humidity sensor C
-
±9.9%
S633
Calibrated humidity sensor C
-
20 – 80%
Service Menu: System / Network Setup Parameters Series S800:
Page 1 of 2, System View
Menu Line
Function
Default
Range
S801 Password
-
-
S802
Number of connected units
-
1 – 16
S803
Teamwork mode
No
No, 1, 2
S804
S805
U2U group
-
1 - 99
S806
S807
S808
S809
Configuration Safe Status
No
No, Save, Load
S810
Network Safe Status
-
No, Save, Load
S811 SW
version:
-
80