Liebert iCOM Microprocessor TM-10098 User Manual
Page 79

iCOM
Controls Training and Service Manual
Service Menu: Set Alarm Parameters: Page 5 of 6
Menu Line
Parameter
S249
Password
S250
DELAY
EN-DIS
TYPE
S251
Working Hours Exceeded
-
En
Warning
S252
Smoke Detected
5 Sec
En
Alarm
S253
Water Under Floor
5 Sec
En
Alarm
S254
Cond Pump-High Water
5 Sec
En
Alarm
S255
Loss of Flow
5 Sec
En
Alarm
S256
Standby Glycol Pump On
5 Sec
En
Alarm
S257
Standby Unit On
5 Sec
En
Alarm
S258
Humidifier Problem
5 Sec
En
Alarm
S259
No Connection w/ Unit 1
-
En
Alarm
S260
Unit X Disconnected
-
En
Alarm
Service Menu: Set Alarm Parameters: Page 6 of 6
Menu Line
Parameter
S262
Password
S263
DELAY
EN-DIS
TYPE
S264
Customer Input 1
5 Sec
En
Alarm
S265
Customer Input 2
5 Sec
En
Alarm
S266
Customer Input 3
5 Sec
En
Alarm
S267
Customer Input 4
5 Sec
En
Alarm
S268
Call Service
5 Sec
En
Message
S269
High Temperature
5 Sec
En
Message
S270
Loss of Air Blower 1
5 Sec
En
Alarm
S271
Reheat Lockout
5 Sec
En
Message
S272
Humidifier Lockout
5 Sec
En
Message
S273
Humid + Reheat Lockout
5 Sec
En
Message
S274
Compressor(s) Lockout
5 Sec
En
Message
78