Control output triac legend, Control output opto-isolator legend – Liebert iCOM Microprocessor TM-10098 User Manual
Page 123

iCOM
Controls Training and Service Manual
Note: Use Pin 5 on the input opto-isolator with reference to the V- terminal
for voltage check. The voltage level is 5 VDC.
Control Output Opto-Isolator Legend:
Opto
Purpose
Opto
Purpose
U1
Reheat 1
U10
Compressor 2
U2
Reheat 2
U11
Econ-O-Cycle Relay (R5)
U3
Reheat 3
U12
Liquid Line Solenoid 1
U4
Humidifier
U13
Hot Gas Bypass 2
U5
Main Fan
U14
Compressor 1
U8
Liquid Line Solenoid 2
U17
CW Actuator
U9
Hot Gas Bypass 2
U18
CW Actuator Close
Note: Use Pin 4 on the output opto-isolator with reference to the correct
transformer neutral/ ground. The voltage level is 24 VAC.
Control Output Triac Legend:
Opto
Purpose
Opto
Purpose
Q1
Reheat 1
Q10
Compressor 2
Q2
Reheat 2
Q11
Econ-O-Cycle Relay (R5)
Q3
Reheat 3
Q12
Liquid Line Solenoid 1
Q4
Humidifier
Q13
Hot Gas Bypass 2
Q5
Main Fan
Q14
Compressor 1
Q8
Liquid Line Solenoid 2
Q17
CW Actuator
Q9
Hot Gas Bypass 2
Q18
CW Actuator Close
122