Controls Training and Service Manual
Small Display Jumper Settings
Jumper
Type
Setting
P4
Manual Contrast
(Rev. 2 only)
* Shunt on Pins 2 & 3
P78
CAN Termination
* Shunt on Pins 2 & 3
P80
BDM Header
* open
P82
Watchdog
(Rev. 2 Only)
* Shunt on Pins 1 & 2
* Default Setting
Temperature/ Humidity Board DIP Switch #1 Settings
Position
Type
Setting
Notes
1
CAN Address
Off
On (if Sensor A)
2
CAN Address
Off
On (if Sensor B)
3
CAN Address
Off
On (if Sensor C)
4
CAN Address
Off
open
5 CAN
Address
On (Normal &
Constant Operation)
Off (Analog Mode)
6
CAN Address
Off (Normal Operation)
On (Analog Mode &
Constant Operation)
7 CAN
Baud
Off
open
8
CAN Baud
Off
open
Temperature/ Humidity Board Jumper Settings
Jumper
Type
Setting
P2
BDM Header
* open
P3
CAN Termination
* Shunt on Pins 2 & 3