Service Menu: Set Alarm Parameters S200 series: Page 1 of 6
Menu Line
Parameter
Default
Range
S201 Password
-
-
S202
Return Sensor Alarms
Enabled
Disabled or Enabled
S203
High Return Temperature
80ºF
34 - 210ºF
S204
Low Return Temperature
65ºF
34 - 210ºF
S205
High Return Humidity
60%
1 – 99%
S206
Low Return Humidity
40%
1 – 99%
S207
Sensor A Alarms
Disabled
Disabled or Enabled
S208
High Temperature Sensor A
90ºF
34 - 210ºF
S209
Low Temperature Sensor A
55ºF
34 - 210ºF
S210
High Humidity Sensor A
70%
1 – 99%
S211
Low Humidity Sensor A
30%
1 – 99%
Service Menu: Set Alarm Parameters: Page 2 of 6
Menu Line
Parameter
Default
Range
S212 Password
-
-
S213
Customer Input 1
Water alarm
See note
S214
Customer Input 1 Active When
Closed
Open or Closed
S215
Customer Input 2
Water alarm
See note
S216
Customer Input 2 Active When
Closed
Open or Closed
S217
Customer Input 3
Water alarm
See note
S218
Customer Input 3 Active When
Closed
Open or Closed
S219
Customer Input 4
Water alarm
See note
S220
Customer Input 4 Active When
Closed
Open or Closed
S221
Warning Activates Alarm Relay
Yes
Yes or No
S222
Reset Disabled Alarms
No
Yes or No
Note: Customer Inputs 1, 2, 3 and 4 messages may be selected from Smoke
Detected, Water Alarm, Condensate Pump Alarm, Flow Alarm, Standby Pump,
Standby Unit.