Liebert iCOM Microprocessor TM-10098 User Manual
Page 84

iCOM
Control Training and Service Manual
Service Menu: Option Setup Parameters S400 series:: Page 2 of 2
Menu Line
Function
Default
Range
S412 Password
-
-
S413
Humidification Enabled
Yes
Yes or No
S414
Infrared Flush Rate
150%
110 – 500%
S415
Dehumidification Enabled
Yes
No or Yes
S416
Electric Reheat Operation
No
No, Normal, Delayed
S417
Single Unit Auto Restart
5 Seconds
0 – 999 seconds
S418
On – Off Enabled
Yes
Yes or No
S419
S420
CW Flush
No
No, 1 – 99 Hours
S421
Freecooling Flush
No
No, 1 – 99 Hours
S422
Hot Water Flush
No
No, 1 – 99 Hours
Service Menu: Service Contacts Parameters S700 series:
Menu Line
Function
Default
Range
S701
Password
-
-
S702
Country
USA
None, United States
S703
Address line 1
-
Text-string
S704
Address line 2
-
Text-string
S705
Address line 3
-
Text-string
S706
Address line 4
-
Text-string
83