iCOM
Control Training and Service Manual
Advanced Menu: Factory Settings Parameters A100 series: Page 2 of 6
Advanced Menu: Factory Settings Parameters A100 series: Page 3 of 6
Menu Code
Function
Default
Range
A101
Password
-
-
A102
Refrigerant Type
R22
R22, R407C
A103
Main Fan Overload
Shut down
Shut down, Disable
A104
Loss of Airflow
Shut down
Shut down, Disable
A105
Number of Compressors
2
0, 1, 2
A106
Compressor Delay Time
0
0 - 120 Sec
A107
Compressor Minimum
On Time
3 Min
0 - 5 Min
A108
Compressor Minimum
Off Time
3 Min
0 - 5 Min
A109
Pump Down
Yes
No, Yes
A110
Capacity Control Type
Unloader
No, Unloader, HGBP,
Digital, Digital + TH
Menu Code
Parameter
Default
Range
A112
Password
-
-
A113
Digi Scroll Cycle
15
No, 10 - 30 Sec
A114
High Temperature Digi
Scroll
268°F
33 - 392°F
A115
Digi Scroll Switchback
250°F
33 - 392°F
A116
Low Pressure Device
Type
Analog Analog,
Switch
A117
Low Pressure Threshold
Phase 1
* See Note 1
0.0 - 145 psiA
A118
Low Pressure Threshold
Phase 2
* See Note 2
0.0 - 145 psiA
85