Ratings

Notes:

1. Shield water heaters require special gas venting. Use

only the vent materials and methods specified in the
Shield Installation and Service Manual.

2. Standard Shield water heaters are equipped to operate

from sea level to 4,500 feet only with no adjustments.
The water heater will de-rate by 4% for each 1,000 feet
above sea level up to 4,500 feet.

3. High altitude Shield water heaters are equipped to

operate from 3,000 to 12,000 feet only with no field
adjustments. The water heater will de-rate by 2% for
each 1,000 feet above 3,000 feet. High altitude models
are manufactured with a different control module
for altitude operation, but the operation given in this
manual remains the same as the standard models. A
high altitude label (as shown in FIG. A) is also affixed
to the unit.

7

Maximum allowed working pressure is located on the rating plate.

Model Number

Note: Change “N”
to “L” for L.P. gas

models.

CSA

Input Modulation Btu/hr

(Note 2)

Water Content

Gallons

Water

Connections

Gas

Connections

Vent/Air Size

Min

Max

(Note 1)

SNR150-100

30,000 - 150,000

92

1-1/2"

1/2"

3"

SNR200-100

40,000 - 199,999

93

1-1/2"

1/2"

3"

SNA285-125

57,000 - 285,000

124

2"

3/4"

4"

SNA400-125

80,000 - 399,999

125

2"

1"

4"

SNA500-125

100,000 - 500,000

126

2"

1"

4"

NOTICE

Figure A High Altitude Label Location

UNIT EQUIPPED FOR

3,000 FT. TO 12,000 FT.

HIGH ALTITUDE

Installation & Service Manual