Sidewall direct venting, Vent/air termination – sidewall, Installation & service manual – Lochinvar Shield SNR150-100 User Manual

Page 23

background image

23

Vent/air termination – sidewall

3

Sidewall direct venting

(continued)

VENT / AIR

TERMINATION

12"

MIN.

12"

MIN.

12"

MIN.

Figure 3-2A Clearance to Gravity Air Inlets

5. Maintain clearances as shown in FIG.’s 3-1A thru 3-3B,

pages 22 and 24. Also maintain the following:
a. Vent

must

terminate:

• At least 6 feet from adjacent walls.

• No closer than 12 inches below roof overhang.

• At least 7 feet above any public walkway.

• At least 3 feet above any forced air intake within

10 feet.

• No closer than 12 inches below or horizontally from

any door or window or any other gravity air inlet.

b. Air inlet must terminate at least 12 inches above

grade or snow line; at least 12 inches below the vent

termination; and the vent pipe must not extend

more than 24 inches vertically outside the building.

c. Do not terminate closer than 4 feet horizontally

from any electric meter, gas meter, regulator, relief

valve, or other equipment. Never terminate above or

below any of these within 4 feet horizontally.

6. Locate terminations so they are not likely to be damaged by

foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.

ALTERNATE VENTING ARRANGEMENT

(IF SPACE PERMITS)

BIRD

SCREEN

12”

MIN

12” MIN

15” MAX

COUPLING

TO BOILER
INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

Figure 3-1C Alternate PVC/CPVC Venting Arrangement
(if Space Allows) w/Field Supplied Fittings

Installation & Service Manual

TM

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

12" MIN

12" MIN

15" MAX

MODELS SNR150-100 THRU SNA500-125

Figure 3-1D Alternate PVC/CPVC/SS Venting
Arrangement - Typical Stainless Steel Sidewall
Termination of Air and Vent w/Field Supplied Fittings,
Utilizing 90° Elbow Intake

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

FROM BOILER

VENT PIPE

CONNECTION

TO BOILER

INTAKE AIR

CONNECTION

BIRD SCREEN

MODELS SNA285-125 THRU SNA500-125 WITH FASNSEAL ONLY

Figure 3-1E Alternate SS Venting Arrangement -
Typical Stainless Steel Sidewall Termination of Air and
Vent w/Field Supplied Fittings, Utilizing FasNSeal’s
Hood Intake