Vertical direct venting, Vent/air termination – vertical – Lochinvar Shield SNR150-100 User Manual

Page 29

background image

29

4

Vertical direct venting

Vent/air termination – vertical

Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death
or substantial property damage.

Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

Determine location

Locate the vent/air terminations using the following
guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting section on page 21
of this manual.

2. The vent must terminate at least 3 feet above the highest

place in which the vent penetrates the roof and at least 2
feet above any part of a building within 10 horizontal feet.

3. The air piping must terminate in a down-turned 180°

return pipe no further than 2 feet from the center of the
vent pipe. This placement avoids recirculation of flue
products into the combustion air stream.

4. The vent piping must terminate in an up-turned coupling

as shown in FIG. 4-1A. The top of the coupling must
be at least 1 foot above the air intake. When the vent
termination uses a rain cap as illustrated in FIG. 4-1B
maintain at least 36" (914 mm) above the air inlet. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than
2 feet apart and with the vent termination at least 1 foot
above the air intake.

Figure 4-1A Vertical Termination of Air and Vent

5. Locate terminations so they are not likely to be damaged by

foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.

ƽ WARNING

NOTICE

ƽ WARNING

Do not connect any other appliance to
the vent pipe or multiple water heaters to
a common vent pipe. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

ƽ WARNING

Installation & Service Manual

TM

Rooftop vent and air inlet terminations
must terminate in the same pressure
zone, unless vertical vent sidewall air is
set up as shown in the General Venting -
Vertical Vent, Sidewall Air Section.

6" (152 MM) MINIMUM

ABOVE ROOF /

SNOW LINE

VENT

COM,BUSTION

AIR

ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” (610 MM)
OF VENT PIPE

VENT OUTLET

36” (914 MM) MINIMUM

ABOVE AIR INLET

BIRD SCREEN

(TYPICAL)

Figure 4-1B Stainless Steel Vertical Termination of Air
and Vent