General venting

3" S.S. ADAPTER

VENT

3" S.S. INTERMEDIATE

(FOR SAF-T VENT ONLY)

Figure 3-11 Near Water Heater Stainless Steel Venting

Stainless steel air intake/vent connections

1. Combustion Air Intake Connector (FIG. 3-11) - Used to

provide combustion air directly to the unit from

outdoors. A fitting is provided on the unit for final

connection. Combustion air piping must be supported

per guidelines listed in the National Mechanical Code,

Section 305, Table 305.4 or as local codes dictate.

2. Vent Connector (FIG. 3-11) - Used to provide a

passageway for conveying combustion gases to the

outside. A transition fitting is provided on the unit for

final connection. Vent piping must be supported per the

National Building Code, Section 305, Table 305.4 or as

local codes dictate.

Table 2B Approved Stainless Steel Terminations and Adapters

Model

ProTech

Heat Fab

Z Flex

FasNSeal

Saf-T Vent

Z-Vent

Water

Heater

Adapter

Flue

Termination

Intake

Air

Termination

Water

Heater

Adapter

Intermediate

Adapter

Flue

Termination

Intake

Air

Termination

Water

Heater

Adapter

Flue

Termination

Intake Air

Termination

SNR150 -

SNR200

300715

FSBS3

FSRC3(R.C)

303889

KB80210 9353BUREZ-1*

9392

5300CI

9314TERM 2SVSLA03

2SVSTP03

2SVSRCX03

2SVSTEX0390

SNA285 -

SNA500

F303759

FSBS4

FSRC4(R.C.)

FSAIH04

303888

KB285600 9454BUREZ-1*

9492

5400CI

9414TERM 2SVSLA04

2SVSTP04

2SVSRCX04

2SVSTEX0490

* = This adapter must be used in addition to the water heater adapter for Saf-T vent pipe as shown in FIG. 3-11, unless approved
vent other than standard diameter is used. Consult a Heat Fab representative for questions.

The Shield water heater uses model specific combustion air
intake and vent piping sizes as detailed in Table 2C below.

Model

Air Intake

Vent

SNR150-100 -- SNR200-100

3 inches

3 inches

SNA285-125 -- SNA500-125

4 inches

4 inches

Table 2C Air Intake/Vent Piping Sizes

Increasing or decreasing combustion air
or vent piping is not authorized.

NOTICE

Models SNA400-125 and SNA500-125 will de-rate 1.75% per
25 feet of vent when installed as direct vent or 0.75% per 25
feet of vent when drawing combustion air from the room.

Models SNR150-100 through SNA285-125 will de-rate up to
1% per 25 feet of vent pipe when installed as direct vent, but
will not de-rate when drawing combustion air from the room.

Minimum / Maximum allowable combustion

air and vent piping lengths are as follows:

Vent = 12 equivalent feet minimum / 100 equivalent feet
maximum

Combustion Air (when used) = 12 equivalent feet minimum /
100 equivalent feet maximum

When determining equivalent combustion air and vent length,
add 5 feet for each 90° elbow and 3 feet for each 45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45°
elbows + (1) concentric vent kit (CVK3003) = 49 equivalent
feet of piping.