Operating information

(continued)

OPERATION

DISPLAY

1. When the tank temperature falls below the set point minus the

differential, the control will start the burner.

HTR: Standby

TANK: 123.8F(129)

2. The control connects 120 VAC to the blower. The blower does

not run at this time.

• The manual reset high limit must be closed before the control
powers up the blower.

• The control starts the internal pump.

• If there is an external limit connected to the heater, it must be
closed.

HTR: Standby

TANK: 123.8F(129)

3. The control then starts a 10 second prepurge cycle.

HTR: PREPURGE

TANK: 123.9F(129)

4. Once the prepurge cycle is complete, and the blocked drain

switch and auto-reset high limit are closed, the control starts the

5 second trial for ignition by sending spark voltage to the spark

electrode and opening the gas valve.

HTR: IGNITION

TANK: 123.9F(129)

5. If the control does not detect flame by the end of the trial for

ignition, the control performs a 10 second postpurge, another

prepurge and tries to light the burner again. If the burner does

not light after 4 trials, the control locks out for 1 hour and then

tries another set of 4 trials.

HTR: POSTPURGE, PREPURGE

TANK: 123.9F(129)

6. If the control detects a flame before the trial for ignition ends, it

begins to modulate the burner in order to maintain the set point.

HTR: RUN 20% RATE

TANK: 124.8F(129)

7. Once the tank temperature goes 3 - 4°F above the set point, the

control will turn off the burner. The blower will remain on for the
10 second postpurge cycle. The internal pump will continue to
run for its pump delay time, then turn off.

HTR: POSTPURGE

TANK: 127.4F(129)

8. Burner off.

HTR: Standby

TANK: 124.7F(129)

Sequence of operation