Troubleshooting – Lochinvar Shield SNR150-100 User Manual

Page 63

background image

63

13

Troubleshooting

(continued)

Table 13A Troubleshooting Chart - No Display

FAULT

CAUSE

CORRECTIVE ACTION

No Display

- No 120 VAC supplied to unit.

• Check external line switch, fuse, or breaker.

• Check wiring harness connection between display
board and main control board. Connect harness at both
points.

- Bad display board.

• Replace board.

- Bad main control board.

• Replace the main control board.

- Blown fuse.

• Replace fuse F3 on the main control board, see

page 62 of this manual.

No Burner

Operation

- Tank temperature set point satisfied.

• Review temperature setting.

- Unit locked out on fault.

• Consult display for specific fault. Refer to fault
descriptions on page 66 of this manual for corrective
actions.

Unit Does

Not Modulate

Above 50%

- Flue sensor open.

• Verify that the flue sensor is located in the flue outlet.

• Check wiring connections at the flue sensor.

• Check the resistance of the flue sensor and compare
to Table 13C on page 64 of this manual.