Determine water heater location

(continued)

Figure 1-6_Combustion Air from Outside - Single
Opening

3. If air is taken from another interior space, each of the

two

openings specified above should have a net free

area of one square inch for each 1000 Btu/hr (22 cm

2

per kW) of input, but not less than 100 square inches

(645

cm

2

) (see FIG. 1-5).

4. If a single combustion air opening is provided to bring

combustion air in directly from the outdoors, the opening

must be sized based on a minimum free area of one square

inch per 3000 Btu/hr (7 cm

2

per kW). This opening must

be located within 12" (30 cm) of the top of the enclosure

(see FIG. 1-6).

IF NECESSARY FOR

TIGHT CONSTRUCTION

Figure 1-5_Combustion Air from Interior Space

Installation & Service Manual

TM

TABLE - 1B

MINIMUM RECOMMENDED COMBUSTION

AIR SUPPLY TO EQUIPMENT ROOM

Model

Number

FIG. 1-3

FIG. 1-4

FIG. 1-5

FIG. 1-6

*Outside Air from

2 Openings Directly from

Outdoors

*Outside Air from

2 Ducts Delivered from

Outdoors

**Inside Air from

2 Ducts Delivered from Interior

Space

*Outside Air from

1 Opening Directly
from Outdoors, in

2

Top

Opening, in

2

Bottom

Opening, in

2

Top

Opening, in

2

Bottom

Opening, in

2

Top

Opening, in

2

Bottom

Opening, in

2

SNR150-100

38

(246 cm

2

)

38

(246 cm

2

)

75

(484 cm

2

)

75

(484 cm

2

)

150

(968 cm

2

)

150

(968 cm

2

)

50

(323 cm

2

)

SNR200-100

50

(323 cm

2

)

50

(323 cm

2

)

100

(646 cm

2

)

100

(646 cm

2

)

200

(1,291 cm

2

)

200

(1,291 cm

2

)

67

(433 cm

2

)

SNA285-125

72

(465 cm

2

)

72

(465 cm

2

)

143

(923 cm

2

)

143

(923 cm

2

)

285

(1,839 cm

2

)

285

(1,839 cm

2

)

95

(613 cm

2

)

SNA400-125

100

(646 cm

2

)

100

(646 cm

2

)

200

(1,291 cm

2

)

200

(1,291 cm

2

)

400

(2,581 cm

2

)

400

(2,581 cm

2

)

134

(865 cm

2

)

SNA500-125

125

(807 cm

2

)

125

(807 cm

2

)

250

(1,613 cm

2

)

250

(1,613 cm

2

)

500

(3,226 cm

2

)

500

(3,226 cm

2

)

167

(1,078 cm

2

)

*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a
duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings.
The above requirements are for the water heater only; additional gas fired appliances in the equipment room will require an
increase in the net free area to supply adequate combustion air for all appliances.

**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”.
For buildings of *“Tight Construction”, provide air openings into the building from outside.

*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet
per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.

*“Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).