beautypg.com

General, Venting, Venting and combustion air – Lochinvar Shield SNR150-100 User Manual

Page 17

background image

17

PVC/CPVC vent piping materials

Use only the materials listed in Table
2A for vent pipe, and fittings. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.

Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

Venting and combustion air

ƽ DANGER

The Shield water heater must be vented and
supplied with combustion and ventilation
air as described in this section. Ensure the
vent and air piping and the combustion
air supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section 1
of this manual.

Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.

Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.

All vent pipes must be glued, properly
supported, and the exhaust must be
pitched a minimum of a 1/4 inch per foot
back to the water heater (to allow drainage
of condensate).

ƽ WARNING

NOTICE

ƽ WARNING

ƽ WARNING

For closet and alcove installations, CPVC
or stainless steel material MUST BE used
in a closet/alcove structure. Failure to
follow this warning could result in fire,
personal injury, or death.

NOTICE

Requirements for installation in Canada

1. Installations must be made with a vent pipe system

certified to ULC-S636.

IPEX is an approved vent manufacturer in Canada

supplying vent material listed to ULC-S636.

2. The first three (3) feet of plastic vent pipe from the

appliance flue outlet must be readily accessible for visual

inspection.

3. The components of the certified vent system must not be

interchanged with other vent systems or unlisted

pipe/fittings. For concentric vent installations, the inner

vent tube must be replaced with field supplied certified

vent material to comply with this requirement.

4. The 3" Concentric Vent Kit available from Lochinvar (see

Section 3 – Sidewall Termination – Optional Concentric

Vent) and the 3" Concentric Vent Kit available from IPEX

are both approved for use on the Shield Water Heater. Both

kits are listed to the ULC-S636 standard for use in Canada.

2

General

venting

(continued)

Installation & Service Manual

TM

This appliance requires a special venting
system. The vent connection to the
appliance must be made with the starter
CPVC pipe section provided with the
appliance if PVC/CPVC vent is to be used.
For stainless steel venting use an adapter
from Table 2B (pg. 20) that corresponds
with the intended vent manufacturer to be
used and discard the CPVC starter piece.
The field provided vent fittings must be
cemented to the CPVC pipe section using
an “All Purpose Cement” suitable for
PVC and CPVC pipe. Use only the vent
materials, primer, and cement specified in
this manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.

Installing vent and air piping

Improper installation of PVC or CPVC
systems may result in injury or death.

ƽ CAUTION

Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.

NOTICE

1. Work from the water eater to vent or air termination. Do

not exceed the lengths given in this manual for the air or

vent

piping.

2. Cut pipe to the required lengths and deburr the inside and

outside of the pipe ends.

3. Chamfer outside of each pipe end to ensure even cement

distribution when joining.

4. Clean all pipe ends and fittings using a clean dry rag.

(Moisture will retard curing and dirt or grease will prevent

adhesion.)

5. Dry fit vent or air piping to ensure proper fit up before

assembling any joint. The pipe should go a third to

two-thirds into the fitting to ensure proper sealing after

cement is applied.