beautypg.com

Operating information, Status display screens – Lochinvar Shield SNR150-100 User Manual

Page 55

background image

55

11

Operating information

(continued)

Status Display Screens

By using the Previous/Next (, ) arrow keys on the electronic control module display panel, you can navigate through the
five (5) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items
and what they can display:

Screen

Display shows:

Description

#1

HTR: OFF

The unit has been turned OFF by the Enter/Reset button on the
electronic control module display panel.

Standby

The unit has not received a call for heat.

Prepurge

The unit has initiated a 10 second purge period on a call for heat.

Ignition

The unit has begun a 5 second spark period to ignite the main burner.

RUN***% Rate

The unit has fired and is running at the displayed percentage.

Postpurge

The call for heat has been satisfied and the unit runs the fan for an
additional 10 seconds to clear the combustion chamber and vent system
of residual flue products.

Service

The unit has been placed in a temporary mode that will allow the unit to
fire at 100% of rate for the purpose of combustion analysis.

TANK:***.*F

The tank temperature is displayed.

Open

The control does not detect the tank sensor.

Shorted

The tank sensor wires or the sensor itself has become shorted.

Press the Next  arrow key on the electronic control module display to access Screen #2.

#2

HEX IN: ***.*F

The temperature at the inlet to the heat exchanger is displayed.

Open

The control does not detect the heat exchanger inlet sensor.

Shorted

The heat exchanger inlet sensor wires or the sensor itself has become
shorted.

HEX OUT: ***.*F

The temperature at the outlet of the heat exchanger is displayed.

Open

The control does not detect the heat exchanger outlet sensor.

Shorted

The heat exchanger outlet sensor wires or the sensor itself has become
shorted.

Press the Next  arrow key on the electronic control module display to access Screen #3.

Status display screens

Installation & Service Manual

TM