beautypg.com

9 replacing the c-plug – Siemens X-400 User Manual

Page 117

background image

Installation and Commissioning

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches
C79000-G8976-C186-03

117

6.9

Replacing the C-PLUG

Removing the C-PLUG

It is only necessary to remove the C-PLUG if there is a problem on the basic de-
vice. After removing the labeling strip, the upper part of the C-PLUG can be care-
fully levered out of the slot on the Switch CPU using a slotted screwdriver until it
can be gripped with your fingers and carefully removed.

Notice
The C-PLUG must only be removed or inserted when the power supply to the de-
vice is turned off.

Inserting the C-PLUG in the Slot

The C-PLUG is on the Switch CPU below the labeling strip. After removing the la-
beling strip, the C-PLUG is inserted in the receptacle with the socket connector
leading. The notch in the casing must be on the right. The C-PLUG is inserted by
pressing it into the receptacle until the C-PLUG is flush with the front surface of the
CPU.

Figure 6-33

Removing the C-PLUG