SIMATIC IPC427C
Operating Instructions, 04/2009, A5E02414743-01

25

Installing/mounting

5

5.1

Permitted mounting positions

NOTICE

The device is approved for operation in closed rooms only.
Ensure that there is a minimum clearance to the other components or the walls of a

housing:

Below at least 100 mm

Above at least 50 mm

Horizontal (preferred position)

Permitted temperatures

Operation with hard disk:

with up to 3 expansion modules

(max. load 9 W): +5 to +40°C

Operation with CompactFlash card and/or SSD drive:

with up to 3 expansion modules

(max. load 9 W): 0 to +45°C

with up to 3 expansion modules

(max. load 9 W) in RAL: 0 to +50°C

Operation with Compact Flash cards:

without expansion modules in RAL: 0 to +55°C

Vertical

(power supply at the top)

Operation with hard disk:

with up to 3 expansion modules

(max. load 9 W): +5 to +40°C

With installed Compact Flash card:

without expansion modules: 0 to +45°C

Operation with CompactFlash card and/or SSD drive:

with up to 3 expansion modules

(max. load 9 W) in RAL: 0 to +45°C

Operation with Compact Flash cards:

with up to 3 expansion modules

(max. load 9 W) in RAL: 0 to +50°C

Notes:
When mounted on a DIN rail, the device should be secured

to prevent shifting (e.g. with a DIN rail ground terminal).