Power requirements, Power requirements -42 – Sun Microsystems StorageTek 96257 User Manual
Page 42
Configuration Planning
2-42
Sun Confidential: Internal Only
96257
Revision A
Power Requirements
Table 2-9. VSM5-VTSS Power Requirements — Single AC Source Power Cable Operation
Number of
16-Drive Arrays
AC Source
Voltage In
AC Source
Amps (Current) In
kVA
kW
Power
Factor
kBTUs
Per Hour
2
264V
10.1A
2.7
2.5
0.95
8.6
208V
12.4A
2.6
2.5
0.98
8.6
180V
16.2A
2.9
2.9
0.99
9.9
3
264V
13.0A
3.4
3.3
0.95
11.1
208V
16.0A
3.3
3.3
0.98
11.1
180V
18.3A
3.3
3.3
0.99
11.1
4
264V
14.5A
3.8
3.6
0.95
12.4
208V
17.8A
3.7
3.6
0.98
12.4
180V
20.3A
3.7
3.6
0.99
12.4
Notes:
• Abbreviations key: A = ampere(s); AC = alternating current; kBTUs = thousand British Thermal Units; kVA =
kilovolt-amperes; kW = kilowatts
Table 2-10. VSM5-VTSS Power Requirements — Dual AC Source Power Cable Operation
Number of
16-Drive Arrays
AC Source
Voltage In
AC Source
Amps (Current) In
*
kVA
kW
Power
Factor
kBTUs
Per Hour
2
264V
5.6A
3.0
2.8
0.95
9.6
208V
6.9A
2.9
2.8
0.98
9.6
180V
7.9A
2.8
2.8
0.99
9.6
3
264V
6.3A
3.3
3.1
0.95
10.7
208V
7.7A
3.2
3.1
0.98
10.7
180V
8.8A
3.2
3.1
0.99
10.7
4
264V
6.9A
3.7
3.5
0.95
11.9
208V
8.5A
3.5
3.5
0.98
11.9
180V
9.8A
3.5
3.5
0.99
11.9
Notes:
•
*
Values are for each line cord; multiply this value by two to obtain the total current for both line cords.
• Abbreviations key: A = ampere(s); AC = alternating current; kBTUs = thousand British Thermal Units; kVA =
kilovolt-amperes; kW = kilowatts