Over The Range Convection Microwave Oven / Installation Manual

4

External exhaust

4.1.2 Outside back exhaust

(example only)

The following chart describes an example of one

possible ductwork installation.

Duct pieces

Equivalent

Length

x

Number

used

=

Equivalent

Length

Wall Cap

40 Ft. (12.2 m)

x (1)

= 40 Ft. (12.2 m)

3 Ft. Straight

Duct (31⁄4” x

10”/8.2 x 25.4

cm Rectangular)

3 Ft. (0.9 m)

x (1)

= 3 Ft. (0.9 m)

90° Elbow

10 Ft. (3 m)

x (2)

= 20 Ft. (3 m)

Equivalent lengths of duct pieces are based on actual tests

and reflect requirements for good venting performance with

any vent hood.

Total Length

= 63 Ft. (19.2 m)

C

For back exhaust, care should be tak-

en to align exhaust with space be-

tween studs, or wall should be pre-

pared at the time it is constructed by

leaving enough space between the

wall studs to accommodate exhaust.

C

If you need to install ducts, note

that the total duct length of 3

1⁄4

” x

10” (8.2 x 25.4 cm) rectangular or

6” (15.2 cm) diameter round duct

should not exceed 120 equivalent

feet (36.5 m).

C

Outside ventilation requires a HOOD

EXHAUST DUCK. Read the following

carefully. It is important that venting

be installed using the most direct

route and with as few elbows as

possible. This ensures clear vent-

ing of exhaust and helps prevent

blockages. Also, make sure dampers

swing freely and nothing is blocking

the ducts.

4.1.3 Exhaust connection

The exhaust adaptor has been designed to mate

with a standard 3

1⁄4

” x 10” (8.2 x 25.4 cm) rectan-

gular duct. If a round duct is required, a rectangu-

lar-to-round transition adaptor must be used. Do

not use less than a 6” 6” (15.2 cm) diameter duct.