ProSoft Technology 5201-DFNT-DNPM User Manual
Page 44
DNPM ♦ ProLinx Gateway
Reference
DNP 3.0 Master
Driver Manual
Page 44 of 56
ProSoft Technology, Inc.
September 30, 2009
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
2 Unsynchronized
Time and Date
CTO
129,
130
07, With
Quant=1
48
Master will process this variation
52 0
Time Delay: All
Variations
1
Time Delay Coarse
129
07, With
Quant=1
16
Master will not process this variation
2
Time Delay Fine
129
07, With
Quant=1
16
Master will not process this variation
60 0 Not
Defined
Not Defined in DNP
1
Class 0 Data
1
06
Master will generate this variation
2
Class 1 Data
1
06, 07, 08
Master will generate this variation
3
Class 2 Data
1
06, 07, 08
Master will generate this variation
4
Class 3 Data
1
06, 07, 08
Master will generate this variation
70 0 Not
Defined
1 File
Identifier
80 0 Not
Defined
1 Internal
Indications 2
00,
Index=7
24
The Master will generate this
variation
81 0 Not
Defined
1 Storage
Object
82 0 Not
Defined
1 Device
Profile
83 0 Not
Defined
Not Defined in DNP
1 Private
Registration
Object
2 Private
Registration
Objection
Descriptor
90 0 Not
Defined
Not Defined in DNP
1 Application
Identifier
100 0
1
Short Floating Point
48
2
Long Floating Point
80
3
Extended Floating
Point
88
101 0
1
Small Packed
Binary-Coded
Decimal
16