beautypg.com

ProSoft Technology 5201-DFNT-DNPM User Manual

Page 41

background image

Reference DNPM

♦ ProLinx Gateway

Driver Manual

DNP 3.0 Master


ProSoft Technology, Inc.

Page 41 of 56

September 30, 2009

OBJECT REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

1 32-Bit

Counter

Change Event
Without Time

129,
130

17, 28

40

Master will process this variation.
Status flags are discarded.

2 16-Bit

Counter

Change Event
Without Time

129,
130

17, 28

24

Master will process this variation.
Status flags are discarded.

3 32-Bit

Delta

Counter Change
Event Without Time

40

4

16-Bit Delta
Counter Change
Event Without Time

24

5

32-Bit Counter
Change Event With
Time

88

6

16-Bit Counter
Change Event With
Time

72

7

32-Bit Delta
Counter Change
Event With Time

88

8

16-Bit Delta
Counter Change
Event With Time

72

23 0 Frozen

Counter

Event: All
Variations

1 32-Bit

Frozen

Counter Event
Without Time

40

2

16-Bit Frozen
Counter Event
Without Time

24

3

32-Bit Frozen Delta
Counter Event
Without Time

40

4

16-Bit Frozen Delta
Counter Event
Without Time

24

5

32-Bit Frozen
Counter Event With
Time

88

6

16-Bit Frozen
Counter Event With
Time

72

7

32-Bit Frozen Delta
Counter Event With
Time

88

This manual is related to the following products: