beautypg.com

Subset definition, 3 subset definition – ProSoft Technology 5201-DFNT-DNPM User Manual

Page 39

background image

Reference DNPM

♦ ProLinx Gateway

Driver Manual

DNP 3.0 Master


ProSoft Technology, Inc.

Page 39 of 56

September 30, 2009

6.3 Subset

Definition

OBJECT REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

1

0

Binary Input: All
Variations

1 06

1

Master will generate this variation

1 Binary

Input

1

06 129,

130

00, 01

1

Master will generate and process this
variation

2

Binary Input with
Status

1

06 129,

130

00, 01

8

Master will generate and process this
variation. Status flags are discarded.

2 0 Binary

Input

Change: All
Variations

1

06, 07, 08

56

Master will generate this variation

1 Binary

Input

Change Without
Time

1

06, 07, 08 129,

130

17, 28

8

Master will generate and process this
variation. Status flags are discarded.

2 Binary

Input

Change With Time

1

06, 07, 08 129,

130

17, 28

56

Master will generate and process this
variation. Status flags and time stamp
are discarded.

3 Binary

Input

Change With
Relative Time

1

06, 07, 08 129,

130

17, 28

24

Master will generate and process this
variation. Status flags and relative
time are discarded.

10 0

Binary Output: All
Variations

1 06

8

1 Binary

Output

1

2 Binary

Output

Status

129,
130

00, 01

8

Master does not use this object type
and will not generate a message or
process this type

12 0

Control Block: All
Variations

88

1

Control Relay
Output Block

3, 4, 5,
6

17, 28

129

Echo of
request

88

Master will generate this variation
and parse the response

2 Pattern

Control

Block

88

3

Pattern Mask

16

20 0

Binary Counter: All
Variations

1, 7, 8,
9, 10

06

32

Master will generate this variation

1 32-Bit

Binary

Counter

129,
130

00, 01

40

Master will process this variation.
Status flags are discarded.

2 16-Bit

Binary

Counter

129,
130

00, 01

24

Master will process this variation

3 32-Bit

Delta

Counter

129,
130

00, 01

40

Master will process this variation.
Status flags are discarded.

4 16-Bit

Delta

Counter

129,
130

00, 01

24

Master will process this variation

5 32-Bit

Binary

Counter Without
Flag

1, 7, 8,
9, 10

06 129,

130

00, 01

32

Master will generate and process this
variation