Error Code

Name

Description

20

DNP message overflow
error (Application Layer
Error)

Application response buffer overflow condition. The
response message from the slave is too long to
transmit.

21

DNP master multi-frame
message error (Application
Layer Error)

Received a multi-frame message from the DNP
master. This application does not support multi-frame
messages from the master.

System Configuration Errors

Error Code

Name

Description

100

Too many binary input
points

Too many binary input points are configured for the
module. Maximum value is 15360.

101

Too many binary output
points

Too many binary output points are configured for the
module. Maximum value is 15360.

102

Too many counter points

Too many counter points are configured for the
module. Maximum value is 480.

103

Too many analog input
points

Too many analog input points are configured for the
module. Maximum value is 960.

104

Too many analog input
points

Too many analog output points are configured for the
module. Maximum value is 960.

105

Too many binary input
events

Too many binary input events are configured for the
module. Maximum value is 400.

106

Too many analog input
events

Too many analog input events are configured for the
module. Maximum value is 400.

107

Invalid analog input
deadband

Deadband value for analog input events is out of
range. Value must be in the range of 0 to 32767.

108

Not enough memory

There is not enough memory in the module to
configure the module as specified.

109

Invalid block transfer delay
for blocks 251 and 252
(error/status blocks)

Block transfer delay value specified is too low.

110

File count invalid

The file count must be in the range of 0 to 6.

111

Invalid file record size

The file record size must be in the range of 1 to 120.

112

Invalid block identification
code for file

The file block transfer code must be in the range of
100 to 120.

DNP Port Configuration Errors

Error Code

Name

Description

212

Invalid DNP address

The DNP address specified in the configuration is not
valid (0 to 65534).

213

Invalid DNP port baud rate

The baud rate code specified in the configuration is
not valid.

219

Invalid DNP data link layer
confirm mode

The data link confirmation mode code is not valid in
the configuration.

220

Invalid DNP data link
confirm time-out

The data link time-out period specified in the
configuration is 0. It must be an integer in the range of
1 to 65535.

222

Invalid DNP select/operate
arm time duration

The select/operate arm timer is set to 0. It must be an
integer in the range of 1 to 65535.

223

Invalid DNP application
layer confirm time-out

The application layer confirm time-out value is set to 0.
It must be an integer in the range of 1 to 65535.

224

Invalid DNP write time
interval

The write time interval is not in the data range in the
configuration. The value must be in the range of 0 to
1440.