6.2 Device

Profile

DNP V3.00
DEVICE PROFILE DOCUMENT

Vendor Name:

ProSoft Technology, Inc.

Device Name:

DNP MASTER (VERSION 2.20)

Highest DNP Level Supported :

Device Function:

For Request: L2

Master

For Responses: L2

Notable objects, functions, and/or qualifiers supported in addition to the highest DNP level stated above (see
attached table for complete list):

The following features are configurable on the module: Collision avoidance

Maximum Data Link Frame Size (octets):

Maximum Application Fragment Size (octets):

Transmitted : 292

Transmitted : 2048

Received : 292

Received : 2048

Maximum Data Link Re-tries:

Maximum Application Layer Re-tries:

Configurable from 0 - 255

None

Requires Data Link Layer Confirmation:

Configurable at module start-up (never, sometimes, & always)

Requires Application Layer Confirmation: