background image

DNPM ♦ ProLinx Gateway

Reference

DNP 3.0 Master

Driver Manual


Page 42 of 56

ProSoft Technology, Inc.

September 30, 2009

OBJECT REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

8

16-Bit Frozen Delta
Counter Event With
Time

72

30 0

Analog Input: All
Variations

1 06

16

Master will generate this variation

1

32-Bit Analog Input 1

06 129,

130

00, 01

40

Master will generate and process this
variation. Data returned will be least
significant 16 bits. Status flag will be
discarded.

2

16-Bit Analog Input 1

06 129,

130

00, 01

24

Master will generate and process this
variation

3

32-Bit Analog Input
Without Flag

1

06 129,

130

00, 01

32

Master will generate and process this
variation. Data returned will be least
significant 16 bits.

4

16-Bit Analog Input
Without Flag

1

06 129,

130

00, 01

16

Master will generate and process this
variation

31 0 Frozen

Analog

Input: All Variations

1 32-Bit

Frozen

Analog Input

40

2

16-Bit Frozen
Analog Input

24

3

32-Bit Frozen
Analog Input With
Time To Freeze

88

4

16-Bit Frozen
Analog Input With
Time To Freeze

72

5

32-Bit Frozen
Analog Input
Without Flag

32

6

16-Bit Frozen
Analog Input
Without Flag

16

32 0 Analog

Change

Event: All
Variations

1

06, 07, 08

24

Master will generate this variation

1 32-Bit

Analog

Change Event
Without Time

1

06, 07, 08 129,

130

17, 28

40

Master will generate and process this
variation. Data returned will be least
significant 16 bits. Status flag will be
discarded.

2 16-Bit

Analog

Change Event
Without Time

1

06, 07, 08 129,

130

17, 28

24

Master will generate and process this
variation. Status flags are discarded.

This manual is related to the following products: