ProSoft Technology 5201-DFNT-DNPM User Manual
Page 43
Reference DNPM
♦ ProLinx Gateway
Driver Manual
DNP 3.0 Master
ProSoft Technology, Inc.
Page 43 of 56
September 30, 2009
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
3 32-Bit
Analog
Change Event With
Time
1
06, 07, 08 129,
130
17, 28
88
Master will generate and process this
variation. Data returned will be least
significant 16 bits. Time value not
stored in database. Status flags are
discarded.
4 16-Bit
Analog
Change Event With
Time
1
06, 07, 08 129,
130
17, 28
72
Master will generate and process this
variation. Time value not stored in
database. Status flags are discarded.
33 0 Frozen
Analog
Event: All
Variations
1 32-Bit
Frozen
Analog Event
Without Time
40
2
16-Bit Frozen
Analog Event
Without Time
24
3
32-Bit Frozen
Analog Event With
Time
88
4
16-Bit Frozen
Analog Event With
Time
72
40 0 Analog
Output
Status: All
Variations
1 06
24
1 32-Bit
Analog
Output Status
40
2 16-Bit
Analog
Output Status
129,
130
00, 01
24
Master does not use this object type
and will not generate a message or
process this type
41 0 Analog
Output
Block: All Variations
24
1
32-Bit Analog
Output Block
40
2
16-Bit Analog
Output Block
3, 4, 5,
6
17, 28
129
Echo of
Request
24
Master will generate this variation
and parse the response
50 0
Time and Date: All
Variations
48
1
Time and Date
2
07, With
Quant=1
48
Master will generate this variation
2
Time and Date With
Interval
80
51 0
Time and Date
CTO: All Variations
1
Time and Date
CTO
129,
130
07, With
Quant=1
48
Master will process this variation